Specifications include, but are not limited to: 2 Each (CU 212020) NATURAL GAS PRESSURE REGULATOR PER THE FOLLOWING SPECIFICATIONS: 1. 2" X 2" FLANGED CONNECTIONS 2. 7.0" WATER COLUMN OUTLET PRESSURE 3. OUTLET SPRING SHALL BE GREEN IN COLOR RANGE: 6" - 9.7" WATER COLUMN 4. RELIEF CAPACITY SHALL BE ABLE TO PROVIDE RELIEF AT NO MORE THAN 7 INCHES ABOVE SET POINT 5. INLET PRESSURE 2.8 PSIG 6. 2-1/2" VENT 7. 1-1/4" ORIFICE, 0 DEGREE 8. ITRON ASSEMBLY POSITION "A" 9. FOR USE WITH 0.60 SPECIFIC GRAVITY NATURAL GAS 10. COLOR A.S.A. #49 GRAY 11. ORIFICE TAG ON REGULATOR 12. LOCK UP NOT TO EXCEED 1" WATER COLUMN ABOVE SET POINT 13. ASSEMBLED AND SHIPPED AS COMPLETE UNIT; 480 Each (CU 207065) HIGH PRESSURE - RESIDENTIAL SERVICE REGULATOR PER THE FOLLOWING SPECIFICATIONS: 1. 3/4" X 1" SCREWED CONNECTIONS; 2. 1" VENT; 3. 1/8" ORIFICE; 4. LOCKUP NOT TO EXCEED 1" W.C. ABOVE SET POINT; 5. SET POINT INLET PRESSURE - 25 PSIG, OUTLET PRESSURE - 6.9" W.C., FLOW - 50 CFH AIR; 6. FOR USE WITH 0.60 SPECIFIC GRAVITY NATURAL GAS; 7. PAINTED ASA #49 GRAY; 8. REGULATORS TO BE LABELED WITH ORIFICE SIZE AND SPRING RANGE; 9. EQUIMETER (ROCKWELL INTERNATIONAL) TYPE 143-80-2, MOUNTING POSITION 105, OUTLET SPRING #143-62-021-16 (RANGE 5" - 8 1/2" W.C.); 10. AMERICAN METER COMPANY 1813C, ASSEMBLY POSITION C-2, OUTLET SPRING COLOR - YELLOW (RANGE 5.5"-8.5"-W.C.); 11. FISHER CONTROLS, TYPE HSR OUTLET SPRING 6-9" W.C., 1" VENT POSITION 3F; 5 Each (CU 211831) GAS PRESSURE REGULATOR PER THE FOLLOWING SPECIFICATIONS: 1. 2 " X 2" FLANGED CONNECTIONS. 2. 7.0" WATER COLUMN OUTLET PRESSURE. 3. OUTLET SPRING SHALL BE GREEN RANGE: 5.0" - 8.2" 4. RELIEF CAPACITY SHALL BE ABLE TO PROVIDE RELIEF AT NO MORE THAN 7 INCHES ABOVE SET POINT. 5. INLET PRESSURE 28 PSIG. 6. 2-1/2" VENT. 7. 5/8" ORIFICE WITH 40 DEGREE LOAD RING. 8. ITRON ASSEMBLY POSITION 5. 9. FOR USE WITH 0.60 SPECIFIC GRAVITY NATURAL GAS. 10. COLOR A.S.A. # 49 GRAY. 11. ORIFICE TAG. 12. LOCK UP NOT TO EXCEED 1" W.C. ABOVE SET POINT...